Can AIC SAS 6G expander vary fan speed based on temperature?


Yes, the fan speed can be modified by SAS expander console commands to setup temperature threshold value.

There is a temperature threshold setting by the expander console port, you can try to set up a higher level on T1 temperature which will get a lower fan speed.

  • Expander JBODs’ fans speed are controlled by temperature threshold.
  • Four temperature settings in Celsius are T1, T2, warning threshold, and alarm (critical) threshold.

 PWM duty cycle

How to configure temperature sensor

Four temperature settings in Celsius are T1, T2, warning threshold, and alarm (critical) threshold.

(A) Get the current temperature settings

cmd> temperature

Temperature in Celsius (t1=20 C, t2=55 C, warning=50 C, alarm=55 C)

(B) Set temperature with new T1=30 C, T2=52 C, warning threshold=48 C, and alarm threshold=54 C. The

new setting will take effect after reset.

cmd> temperature 30 52 48 54

cmd> reset

3

Last update:
2016-06-16 08:07
Author:
Johnny Chiang
Revision:
1.5
Average rating: 5 (1 Vote)

You cannot comment on this entry

Chuck Norris has counted to infinity. Twice.